Table Explosion Protection Specs
Specification | Details |
---|---|
EU Directive | 2014/34/EU (ATEX114) |
ATEX Marking Gas (Indoor Unit) | 3G Ex h ic nAC IIB (+H2) T4 Gc |
ATEX Marking Gas (Outdoor Unit) | II 3G Ex h nAC IIB (+H2) T3 Gc |
ATEX Marking Dust (Indoor Unit) | II 3D Ex tc h IIIB T140°C Dc |
ATEX Marking Dust (Outdoor Unit) | II 3D Ex tc h IIIB (+H2) T150°C Dc |
Key Features Bulletpoints
- Explosion-proof modification of the Daikin FTXM + RXM series for safe use in hazardous environments
- Suitable for both cooling and heating operations
- Approved for ATEX zone 2 and 22, ensuring safe use in explosive gas and dust atmospheres
- Operational temperature range between -20°C and +50°C, covering various ambient conditions
- Uses environmentally-friendly R32 refrigerant, with an option for R410a retrofit if needed
- Tailored for industries like Oil & Gas, Marine, and Chemical sectors, ensuring a safe working environment in hazardous locations
- Modified and certified by Ex-Machinery, ensuring the product meets explosion-proof standards
Optional features
The ATEX-modified Daikin air conditioners offer versatile configurations to meet different industrial needs. Three setup options are available: an indoor unit for ATEX zone 2 with an outdoor unit for a safe area, an indoor unit for a safe area with an outdoor unit for ATEX zone 2, or both units designed for ATEX zone 2 environments. For enhanced durability in marine settings, a corrosion protection upgrade with AISI 316 fasteners is offered. Additional options include R410A refrigerant retrofitting, 50Hz/60Hz frequency upgrades, and seamless connection to Building Management Systems (BMS) or Industrial Distributed Control
Systems (DCS).
Specification | Details |
---|---|
Model Names | Ex-M FTXM20, Ex-M FTXM25, Ex-M FTXM35, Ex-M FTXM42, Ex-M FTXM50, Ex-M FTXM60, Ex-M FTXM71 |
Cooling Capacity | 3.5 kW to 14.0 kW |
Heating Capacity | 4.0 kW to 16.0 kW |
Operating Range Cooling | -20°C to +50°C |
Operating Range Heating | -20°C to +24°C |
Refrigerant | R32 (with optional R410a retrofit) |
Power Supply | 1Phase, 220-240V, 50Hz (60Hz on request) |
Outdoor Unit Dimensions (mm) | 734x954x401, 990x940x320, 1,430x940x320 |
Weight | 32 kg, 49 kg |
- Le choix d'une sélection entraîne l'actualisation de la page entière.
- S'ouvre dans une nouvelle fenêtre.