Table Explosion Protection Specs
Description | Details |
---|---|
EU Directive | 2014/34/EU (ATEX114) |
ATEX Marking Gas (Indoor Unit) | 3G Ex h ic nAC IIB (+H2) T4 Gc |
ATEX Marking Gas (Outdoor Unit) | II 3G Ex h nAC IIB (+H2) T3 Gc |
ATEX Marking Dust (Indoor Unit) | II 3D Ex tc h IIIB T140°C Dc |
ATEX Marking Dust (Outdoor Unit) | II 3D Ex tc h IIIB (+H2) T150°C Dc |
Key Features Bulletpoints
- Explosion-proof modification of the Daikin FCAG + RXM series for safe use in hazardous environments
- Suitable for both cooling and heating operations
- Approved for ATEX zone 2 and 22, ensuring safe use in explosive gas and dust atmospheres
- Operational temperature range between -20°C and +50°C, covering various ambient conditions
- Uses environmentally-friendly R32 refrigerant, with an option for R410a retrofit if needed
- Tailored for industries like Oil & Gas, Marine, and Chemical sectors, ensuring a safe working environment in hazardous locations
- Modified and certified by Ex-Machinery, ensuring the product meets explosion-proof standards
Optional features
The ATEX Cassette Airco offers several optional features to enhance its performance and suitability for various environments. For applications requiring higher durability, a marine upgrade is available, providing additional corrosion protection on fins, coils, and outdoor casings. Users can opt for an R410a retrofit, replacing the standard R32 refrigerant, and a 50Hz/60Hz upgrade to accommodate different electrical systems. Additional safety and convenience can be achieved with a rugged IP66 casing wired remote control, offshore corrosion resistance treatment, and an ATEX isolating switch for maximum safety in hazardous areas.
Description | Details |
---|---|
Model Names | ExM FCAG35B, ExM FCAG50B, ExM FCAG60B |
Cooling Capacity | 3.5 kW to 14.0 kW |
Heating Capacity | 4.0 kW to 16.0 kW |
Operating Range (Cooling) | -20°C to +52°C |
Operating Range (Heating) | -20°C to +24°C |
Refrigerant | R32 (with optional R410a retrofit) |
Power Supply | 1Phase, 220-240V, 50Hz (60Hz on request) |