Table Explosion Protection Specs
Specification | Details |
---|---|
EU Directive | 2014/34/EU (ATEX114) |
ATEX marking gas (indoor unit) | 3G Ex h ic nAC IIB (+H2) T4 Gc |
ATEX marking gas (outdoor unit) | II 3G Ex h nAC IIB (+H2) T3 Gc |
ATEX marking dust (indoor unit) | II 3D Ex tc h IIIB T140°C Dc |
ATEX marking dust (outdoor unit) | II 3D Ex tc h IIIB (+H2) T150°C Dc |
Applied Standards |
EN 60079-0, EN 60079-11, EN 60079-15, EN 60079-31, EN 80079-36, EN 80079-37 |
Key Features Bulletpoints
- Certified for ATEX zone 2 and zone 22 environments
- Designed for high ambient temperatures up to 52°C
- Capable of both cooling and heating
- Energy-efficient operation with low power consumption
- Quiet operation with minimal noise levels
- Corrosion protection coating for industrial and marine environments
- Seamless integration with Building Management Systems (BMS) and Distributed Control Systems (DCS)
- Available in multiple capacities to suit various application needs
Create a clear and concise headline that summarizes one of the product's benefits
The Ex Ducted Airco offers several optional features to enhance its performance and suitability for various environments. For applications requiring higher durability, a marine upgrade is available, providing additional corrosion protection on fins, coils, and outdoor casings. Users can opt for an R410a retrofit, replacing the standard R32 refrigerant, and a 50Hz/60Hz upgrade to accommodate different electrical systems. Additional safety and convenience can be achieved with a rugged IP66 casing wired remote control, offshore corrosion resistance treatment, and an ATEX isolating switch for maximum safety in hazardous areas.
Specification | Details |
---|---|
Model Names | ExM FBA35A, ExM FBA50A, ExM FBA60A, ExM FBA71A, ExM FBA100A, ExM FBA125A, ExM FBA140A |
Cooling Capacity | 3.5 kW to 14.0 kW |
Heating Capacity | 4.0 kW to 16.0 kW |
Operating Range |
Cooling: -20°C to +52°C Heating: -20°C to +24°C |
Refrigerant | R32 (with optional R410a retrofit) |
Power Supply | 1Phase, 220-240V, 50Hz (60Hz on request) |
Indoor Unit Dimensions (mm) | 245x700x800, 245x1,000x800 |
Indoor Unit Weight (kg) | 28, 35 |
Outdoor Unit Dimensions (mm) | 734x954x401, 990x940x320, 1,430x940x320 |