Table Explosion Protection Specs
Specification | Details |
---|---|
EU Directive | 2014/34/EU (ATEX114) |
ATEX Marking Gas (Indoor Unit) | 3G Ex h ic nAC IIB (+H2) T4 Gc |
ATEX Marking Gas (Outdoor Unit) | II 3G Ex h nAC IIB (+H2) T3 Gc |
ATEX Marking Dust (Indoor Unit) | II 3D Ex tc h IIIB T140°C Dc |
ATEX Marking Dust (Outdoor Unit) | II 3D Ex tc h IIIB (+H2) T150°C Dc |
Applied Standards | EN 60079-0, EN 60079-11, EN 60079-15, EN 60079-31, EN 80079-36, EN 80079-37 |
Key Features Bulletpoints
- Certified for ATEX zone 2 and zone 22 environments
- Advanced Wind-Free™ Cooling technology for gentle, uniform cooling
- Energy-efficient operation, reducing consumption by up to 77%
- Quiet operation with noise levels as low as 21 dB(A)
- Corrosion protection coating on fins and coils for marine and industrial environments
- Seamless integration with BMS and industrial DCS systems
- Available in multiple configurations to suit various installation needs
Optional features
The ATEX Wall Mount Airco offers a range of optional features to enhance its performance and suitability for various environments. For applications requiring enhanced durability, a marine upgrade is available, providing additional corrosion protection on fins, coils, and outdoor casings. Users can also opt for an R410a retrofit, replacing the standard R32 refrigerant, and a 50Hz/60Hz upgrade to accommodate different electrical systems. For added convenience and safety, a rugged IP66 casing wired remote control can be included, along with an offshore corrosion resistance treatment. An ATEX isolating switch is also available, ensuring maximum safety in hazardous areas.
Types | |||
---|---|---|---|
Ex-M AC026TNXDKG | Ex-M AC035TNXDKG | Ex-M AC052TNXDKG | Ex-M AC071TNXDKG |
Nominal cooling capacity | |||
2.6 kW |
3.5 kW | 5.2 kW | 7.1 kW |
8900 BTU | 11900 BTU | 17100 BTU | 24200 BTU |
0.7 RT | 1 RT | 1.4 RT | 2 RT |
Nominal heating capacity | |||
3.3 kW | 4.0 kW | 5.0 kW | 7.1 kW |
11300 BTU | 13600 BTU | 20500 BTU | 24200 BTU |
0.9 RT | 1.1 RT | 1.7 RT | 2.3 RT |
Indoor Unit Dimensions
(mm) -
|
|||
820x299x215 | 820x299x215 | 1055x299x215 | 1055x299x215 |
9.1 KG | 9.1 KG | 11.7 KG | 12.7 KG |
Electrical Supply | |||
1Phase, 220-240V,
50/60Hz
|
1Phase, 220-240V,
50/60Hz
|
1Phase, 220-240V,
50/60Hz
|
1Phase, 220-240V,
50/60Hz
|
Operating Range Cooling | |||
-15 °C + 46 °C | -15 °C + 46 °C | -15 °C + 50 °C | -15 °C + 50 °C |
Operating Range Heating | |||
-20 °C + 24 °C | -20 °C + 24 °C | -20 °C + 24 °C | -20 °C + 24 °C |
Refrigerant | |||
R32 (R410-A Optional) | R32 (R410-A Optional) | R32 (R410-A Optional) | R32 (R410-A Optional) |