Table Explosion Protection Specs
Specification | Details |
---|---|
EU Directive | 2014/34/EU (ATEX114) |
ATEX Marking Gas (Indoor Unit) | 3G Ex h ic nAC IIB (+H2) T4 Gc |
ATEX Marking Gas (Outdoor Unit) | II 3G Ex h nAC IIB (+H2) T3 Gc |
ATEX Marking Dust (Indoor Unit) | II 3D Ex tc h IIIB T140°C Dc |
ATEX Marking Dust (Outdoor Unit) | II 3D Ex tc h IIIB (+H2) T150°C Dc |
Key Features Bulletpoints
- Explosion-Proof Modification of the Daikin FHA + RXM Series – Designed for safe use in hazardous environments.
- Suitable for Both Cooling and Heating Operations.
- Approved for ATEX Zone 2 and 22 – Ensuring safe use in explosive gas and dust atmospheres.
- Operational Temperature Range – Functions between -20°C and +50°C, covering various ambient conditions.
- Environmentally-Friendly Refrigerant – Uses R32 refrigerant, with an option for R410a retrofit if needed.
- Industry-Specific Design – Tailored for industries like Oil & Gas, Marine, and Chemical sectors, ensuring a safe working environment in hazardous locations.
- Certified Explosion-Proof Standards – Modified and certified by Ex-Machinery to meet explosion-proof requirements.
Optional features
The ATEX-modified Daikin air conditioners offer versatile configurations to meet different industrial needs. Three setup options are available: an indoor unit for ATEX zone 2 with an outdoor unit for a safe area, an indoor unit for a safe area with an outdoor unit for ATEX zone 2, or both units designed for ATEX zone 2 environments. For enhanced durability in marine settings, a corrosion protection upgrade with AISI 316 fasteners is offered. Additional options include R410A refrigerant retrofitting, 50Hz/60Hz frequency upgrades, and seamless connection to Building Management Systems (BMS) or Industrial Distributed Control Systems (DCS).
Specification | Details |
---|---|
Model Names | ExM FHA35A, ExM FHA50A, ExM FHA60A |
Cooling Capacity | 3.5 kW to 7.1 kW |
Heating Capacity | 4.0 kW to 8.0 kW |
Operating Range | Cooling: -20°C to +52°C, Heating: -20°C to +24°C |
Refrigerant | R32 (with optional R410a retrofit) |
Power Supply | 1Phase, 220-240V, 50Hz (60Hz on request) |
Indoor Unit Dimensions (mm) | 245x700x800, 245x1,000x800 |
Indoor Unit Weight (kg) | 28, 35 |
Outdoor Unit Dimensions (mm) | 734x954x401, 990x940x320, 1,430x940x320 |